LIFT UPS 6-40 KVA (3ph-3ph)

Bypass Facility :-Manual (Through Rotary Switch) / Static Bypass Switch (10 - 18 msec C/O time)*

Audible Noise :- Less Than 60 dB at 1 meter

Design ambient :- 0-50o C

Relative Humidity :- Max. 95 % Non Condensing

Enclosure :- M.S. Powder coated with castor wheels (Turbo Model without Castor wheels)

Dimensions in mm (LxWxH) :- 770x420x750- 980x500x850 - 980x500x850- 1200x570x1000

Communication:- GSM Modem for SMS Alerts to user and service center for any Fault condition, eARD

Input Auto Phase Corrector :- Builtin Input Auto Phase Correction provided in case of i/p supply Phase Reversal

Healthy Phase Selector :-For 1 ph Input UPS Healthy Phase Selector in case of Mains Supply Single Phasing

Wider Input Range :- Input supply range can be extended as per site requirement, helpful in case of Rural or sites with heavy fluctuation of mains supply

TECHNICAL SPECIFICATIONS LIFT UPS 6 - 40 KVA
(3 ph- 3 ph)
Model ELOS-06 ELOS-08 ELOS-12 ELOS-15 ELOS-20 ELOS-25 ELOS-30 ELOS-40
KVA 6 8 12 15 20 25 30 40
DC BUS 4.8 KW 6.4 KW 9.6 KW 12 KW 16 KW 20 KW 24 KW 32 KW
100 % Unbalanced Laod* (optional)

AC INPUT

Input voltage 415 VAC +15, - 20 % / 230VAC +15, -20% *
Input Frequency 50 Hz +/- 6 %

DC CHARGER

Battery Voltage 72V-96V 96V-180V 144V - 240V 240V-360V 360V
Rectifier ATM Tech. Boost and Float mode

AC OUTPUT

Technology Mosfet / IGBT Based PWM Inverter using Micro Controller
Output voltage 400 VAC +/- 2 %
Output Frequency 50 Hz +/- 0.5 %
Output Power factor 0.8 to 1 lag
Output waveform PWM Sine wave
Phase Displacement 120⁰ + 1⁰
Crest Factor 4:1
Galvanic Isolation Inbuilt Galvanic Isolation Transformer Provided
Harmonic Distortion Less than 3 % on Linear Load
Transient Recovery + 4 % from 0 to Full load and corrected within 60 msec.
Inverter Efficiency 87 % - 93 % Depending on DC voltages

INDICATIONS & ALARMS

Indications Mimic Display*, Mains on, Inverter On, Battery Low, Over Load, Output Under
Voltage, Output Over Voltage, DC Over Voltage, I/p Single Phasing / Phase Reversal
Audible Alarm Intermittent beep for 30 sec. On mains fail. Battery low pre-alarm at 80 % of
Battery discharge. Intermittent Beep for all other Trip Conditions

eARD - EMERGENCY AUTO RESCUE DEVICE*

eARD Micro controller based Wireless Digital Scrolling with Voice messeging - To
Display the status - Lift is running on Mains, Lift on Battery, Battery % charge
remaining, Battery Low Pre-alarm, Battery Low - DO NOT USE LIFT, Mains
Supply Single Phasing- Call Electricity Board PH. No.---, Mains Supply Phase
Reversal - Call Electrician PH. No.----, Project Developed By ----, RENUTRON
Service Helpline No. 9371776979

METERING

Digital Metering and Fault Indications Micro controller based Digital Scrolling LCD to Display* - I/P voltage , O/P Voltage, Load Current, Load %, Charging Current, Battery Voltage, % Battery Charge.
Fault indications – Mains Off, O/p under voltage / over voltage, Battery Low pre alarm & Trip, DC Over voltage, Output Overload, I/p under voltage / over voltage, I/p Single Phasing / Phase Reversal

PROTECTIONS

Protections Output Overload (110% -Continuous, 150% - 30 Sec, 300% - 5 seconds), Output short circuit, Battery low trip, DC over voltage, Output under voltage / over voltage, Input under voltage / over voltage, I/p Single Phasing / Phase Reversal, Over Temperature, Input Surge Protection through MOV, Common ELCB at UPS output for multiple Lifts*